TEMPERATURE / HUMIDITY REGULATOR LB-474
thermometer / psychrometer / microprocessor controller
|
![]() |
DESCRIPTION
Controller LB-474 is a microprocessor temperature or humidity regulator. The regulator can be used for controlling such devices as i.e. a wood drying chamber, an injection moulding machine, an incubator, a hot bath etc.
The device’s thermometers perform measurement of two temperatures
using the outside sensors with a platinum thermoresistor Pt1000 (or
optionally Pt100). Using the platinum thermoresistors assures high
measurement accuracy and constant thermometer characteristics. The
outside temperature sensors are made in the casings adjusted in
construction to individual requirements. Different versions of the sensor casings allow on
measurement of different media in various scopes of temperatures. Two
thermometers can also create a psychrometer (based on a principle of
the wet bulb and dry thermometers) what allows on measurement and
regulation of air temperature and humidity independently. The
temperature sensors are attached to the regulator using two or four
cables with the clamps.
Temperature measurement path is calibrated by a producer and the calibration data is stored in the panel in a digital form. The controller does not have any mechanical calibration elements (i.e. potentiometers). The device’s calibration is performed by sending the calibration data obtained in the standard climate conditions through a digital interface to a non-volatile calibration memory of a thermometer. It guarantees comfort and high calibration accuracy as well as stability of the device’s meteorological parameters in time.
The user has a possibility of (by using two key buttons) setting the required work parameters in the regulator. The regulation works based on PID algorithm. PID regulation parameters can be set by the user, after attaching the regulator to a PC computer (on which a special service program had been started) or from a keyboard.
The regulator LB-474 has five control outputs with the transistor key outputs, designed for controlling the external transmitters in (i.e. in a form of an external transmitters of block LB-475). Optionally it can have an analogue output 0..10V or 4..20mA for controlling other devices.
Through a series voltage interface RS-232 the device can be attached
to any computer system, what allows on remote collection of the current
measurement results.
The device is designed for application in stationary conditions, its casing has attachments allowing on assembly on a standard rail TS35. The panel has a big, easy to read LED display allowing on display of two temperatures: set (10 mm) and intended (25 mm). The device is powered from the energy network 230V.
The regulator with the temperature sensors, adequately to an
order, can have an individual calibration
certificate concerning temperature / humidity measurement path from
the Calibration Laboratory LAB-EL.
TECHNICAL DATA
| TEMPERATURE MEASUREMENT |
|||
|---|---|---|---|
| Version |
Scope of measurement |
Measurement inaccuracy with individual sensor
calibration |
Measurement inaccuracy without individual sensor calibration |
| LB-472 | -150..259°C | +/- 0,1°C, +/- 1 last digit (in the scope 50°C) | +/- 1,5°C, +/- 1 last digit |
| MEASUREMENT READINGS |
||
|---|---|---|
| Parameter |
Scope of reading | Resolution displayed |
| Temperature – basic scope |
-99,9..+99,9°C | 0,1 or 1°C |
| Temperature – extended scope |
-150..+259°C | 1°C |
| POWER SUPPLY, CONTROL OUTPUT | |
|---|---|
| network power supply | 230V 50 Hz |
| energy consumption |
5 VA |
| control outputs fan-out (thermoresistor keys) |
40 V / 500 mA / DC |
| type of fan-out | resistance or a transmitter coil |
| SCOPE OF WORK TEMPERATURES |
||
|---|---|---|
| Device | Scope |
Comments |
| Regulator LB-474 | 0..+50°C | |
| Temperature sensor |
-60..+90°C | basic range, limited additionally
by a temperature sensor's construction |
| -150..+259°C | extended range, limited additionally by a temperature sensor’s construction |
|
| RECOMMENDED CONSTANT WORK CONDITIONS LB-472 | |
|---|---|
| Scope of temperatures |
10..40°C |
| Scope of humidity |
20..80% |
| Level of environment corrosion aggressiveness according to PN-71/H-04651 | B |
| Class of resistance according to DIN40050 | IP40 |
INTERFACE I - voltage
Series RS232C, 3 lines (RxD, TxD, GND), transmission parameters: 9600
bps, 8 bits of information, without evenness control, 1 stop bit.INTERFACE FUNCTIONS I
Possibility of reading the measurement results and storing the device's calibration results in its non-volatile memory.INTERFACE II - current
Series so called digital current loop, 1 line
TXD (TXD line active status complies with 25 mA current, in the rest
stage 15 mA), transmission parameters time in accordance with RS232C:
300 bps, 7 bits of information, without evenness control, 1 stop bit.INTERFACE FUNCTIONS II
Possibility of sending the measurement results automatically to long distances in big measurement systems (i.e. to a multi-sensor climate supervision system - see LB-473). Output with a galvanic isolation.OVERALL DIMENSIONS
Panel casing (to be hanged on a rail TS35) overall dimensions: 158 x 90 x 58 mm.Attention: The device should be installed inside an additional outside casing, i.e. wall switch gear. Climate category of the additional outside casing has to be adjusted to the conditions dominating in the place of installation. No cables are supplied with the device (including a power supply cable) as an installation component for only an authorized person.
EQUIPMENT
- cable for the interface RS232C,
- program "User's Interface" for a PC computer.